The product adopts a modular design that can be arbitrarily arranged according to different design schemes and is a perfect combination of a common box unit and an extended unit, which can satisfy the needs of various secondary substations for the flexible use of compact switchgear. The SS series switchgear devices are fully sealed systems, with all live parts and switches enclosed within stainless steel enclosures. They are immune to environmental influences and provide reliable operation. The products are characterized by compact structure, maintenance-free operation, and long lifespan, meeting the requirements for both indoor and outdoor operation. The products have passed the type test certification of the national-level High Voltage Apparatus Testing Center and are widely used in various fields including distribution substations, box-type switchgear, industrial and mining enterprises, airports, railways, commercial areas, high-rise buildings, highways, subways, tunnels, and harsh environmental conditions.
Description
GEE SS SERIES COMPACT-RING MAIN UNIT UP TO 17.5 KV
- Reliable solution for power distribution networkSF6 gas for insulation and for load break switching functions
- Vacuum technology for fault breaking (VCB)
- Self-power relay for high level of protections in all conditions
- Reliable breaker mechanism operation with low power trip coil
- High quality full welded tank IP 67 with leakage rate less than 0.1% per year
- High protection against pollution and humidity by enclosure lP54
- Maintenance free and expected life of the product more than 30 years
- Safe and easy operation with full interlocking system and padlock options
- Integrated cable test facility
- Full Automation /smart functions
TYPE TESTED IN LABORATORIES ACCORDING IEC:
- Dielectric tests:
- Measurement of the resistance of circuits
- Temperature-rise tests
- Verification of the protection
- Short-time withstand current and peak withstand current
- Internal arc tests (tank and cable compartments) Accessibility type A (sides FLR)
- short-circuit making and breaking test duties
- Making and Breaking test duties for switches
- Mechanical Endurance
IEC-62271-200 | metal-enclosed switchgear and controlgear |
IEC-62271-1 | AC switchgear and controlgear |
IEC-62271-103 | AC switches |
IEC-62271-100 | Circuit Breaker Standards |
IEC-62271-102 | AC disconnectors and earthing switches |
IEC 62271-213 | Voltage detecting and indicating system |
GEE SS series- switchgear operates under normal indoor conditions:
Maximum temperature: +75°C
Minimum temperature: -40°C
24-hour average maximum temperature: +35°C
Humidity: Maximum average relative humidity (2 4-hour measurement) 95%
Maximum average relative humidity(1 month measurement) 90%
In the case of installation without reducing the gas pressure: the maximum altitude is 1500 m
GEE SS series- switchgear applications in outdoor operation:
Altitude:≤4000m
Ambient temperature: maximum temperature: +50 °C; The average temperature within 24h does not exceed +35°C
Ambient humidity: 24h relative humidity average does not exceed 95%; The average monthly relative humidity doesn’t exceed 90%
Installation environment: the surrounding air is free of explosive and corrosive gases, and there is no violent vibration in the installation site impact, pollution level does not exceed THE lll. level in GB/T5582;
Ground acceleration caused by earthquakes: below the horizontal direction. 3g, Vertically below. 15g
DIMENSIONS
name | W | D | H |
3 ways-conventional | 1450 | 970 | 1600 |
4 ways-conventional | 1850 | 970 | 1600 |
3 ways-Automated (Smart) | 1450 | 970 | 1850 |
4 ways-Automated (Smart) | 1850 | 970 | 1850 |
★LTL : 3ways
★LLTL : 4ways
★LTTL : 4ways
★LLL : 3ways (switching RMU)
★LLLL : 4ways (switching RMU)